Search results for query: *

  1. E

    Grounding the dish

    Well another tech came by over the weekend to clean up the cable. The dish did not get grounded. Tech told the GC that it is grounded at the box. The splitters will be concealed after the finish goes up. GC brought this up with the tech and the tech said he did not care. Oh well, I am just the...
  2. E

    Grounding the dish

    One last question (I hope) Can the ground wire be ran through the structure or does it need to be exposed all the way to the service?
  3. E

    Grounding the dish

    Bottom line is that the tech should get out there and ground the dish all the way back to the service. Correct?
  4. E

    Grounding the dish

    We are required to have a #6 to the intersystem bonding bridge for use by communication systems such as CATV, Phone and Satellite. What is run from it to these services I believe is at the discretion of said services.
  5. E

    Grounding the dish

    So the tech would need to run #6 instead of #10 due to the distance? Wire size aside, the tech should be able to do this? And I think something was stated about having to run the coax all the way to the service and then back to the splitter. Then again, I had a hard time understanding what the...
  6. E

    Grounding the dish

    I am an electrician doing an addition on a house. I had to move the main service/panel(s) to a new location which is an additional ~50'. Direct TV came out today to bond the dish to the new service location but did not. I am not quite understanding what this tech is wanting and neither is the...