You make a couple critical errors.
Section 800 does not apply to TV antennas or satellite dishes as you state. It does not apply to any form of antenna distribution system. Any part of 800 cannot be used to argue that 5 foot ground rods are allowed for satellite, cable, or MATV.
Article 800 applies to Telephone, telegraph (except radio), outside wiring for Fire Alarm and burglar alarm, and similar central station systems: telephone systems not connected to central station systems but using similar types of equipment. methods of installation and maintenance.
Like I said before NO ONE should trust what is said in these forums. You have fallen victim to that very thing.
There is a revision to the 2002 NEC, 800.40A4 (communication cable) and 820.40A4 (Community Antenna TV), that states that the ground wire for communication circuits entering 1 and 2 family dwellings be less than 20 feet. If the building grounding system is more than 20' away, a ground rod shall be driven, and that rod shall also be bonded to the building ground with a #6 wire. The rod must be at least 5'x1/2".
That text in red does NOT appear in the 2002 NEC. As stated Article 800 does not apply to satellite or cable TV, so any part of that is meaningless. Article 820.40(A)(4) says this.
(4) Length.
The grounding conductor shall be as short as practicable. In one- and two-family dwellings, the grounding conductor shall be as short as practicable, not to exceed 6.0 in (20 ft) in length.
Exception: In one- and two-family dwellings where it is not practicable to achieve an overall maximum grounding conductor length of 6.0 m (20 ft), a separate ground as specified in 250.52(A)(5), (6), or (7) shall be used, the grounding conductor shall be grounded to the separate ground in accordance with 250. 70, and the separate ground bonded to the power grounding electrode system in accordance with 820.40(D).
(D) Bonding of Electrodes. A bonding jumper not smaller than 6 AWG copper or equivalent shall be connected between the community antenna television system' s grounding electrode and the power grounding electrode system at the building or structure served where separate electrodes are used.
Added to the 2005 code
FPN: Similar grounding conductor length limitations applied at apartment buildings and commercial buildings will help to reduce voltages that may be developed between the building's power and communications systems during lightning events.
Your whole part on supplemental grounding does not apply to satellite, cable or MATV. The NEC says when a metal water pipe is used as a grounding electrode it shall be supplemented with ground rod. NEC 2002 Article 250.53(D)
This article has no bearing on satellite.
The NEC is very simple to understand. The problem starts when people do not actually READ the NEC and trust what others say. Another problem is the attempt to apply parts of the NEC that do not apply.
If you read nothing else please read the next section. It will make you think, I promise.
Here are the basic truths about satellite and antenna grounding.
To meet the NEC requirements, you must ground your mast and coax in accordance to 810. The coax must also comply with 820 (810.3), but that does not remove the requirements to meet 810, it only adds additional codes, not provide in 810.
This is were most people miss the boat. 820 is used for the installation methods and types of coax cable ie.. fire rating. The grounding section of 820 (820 section 3) is almost word for word the same as 810. The only major difference is the size of the grounding conductor. 820 says 14 awg, whereas 810 says 10 awg copper, 8 awg aluminum or 17 awg CCS. This is were things get a little interesting.
If you ground the mast using 17 awg CCS, you can ground the coax using 14 awg copper. Or can you? As long as you can argue that 14 awg copper has lower resistance than 17 awg CCS, you should have no problem. Remember, you must meet both 810 and 820. 810 does not mentioned the use 14 awg. It only mentions 10 awg copper, 8 awg aluminum, and 17 awg CCS. Since 17 awg CSS has more resistance than 14 awg, you cannot use that for the coax since it fails to meet the 820 requriement of 14 awg. Since 810 does not say you can use 14 awg, that only leaves 10 awg. However, if your local authoriteis agree that 14 awg copper exceeds the properties of 17 awg CCS (who would not agree) , you can use 14 awg copper, and meet NEC. You may not meet other requirements, but you will meet NEC
So why then do we use 10 awg???
Because every installer has been trained to connect the mast ground to the ground block and then use 10 awg to ground the ground block. This practice is not technically allowed under the NEC. The mast ground and the coax ground are required to be grounded to the same proper grounding points. When you ground the mast to the ground block, you are not grounding to an ground point allowed for under the NEC. You are in effet piggy-backing two grounding wires to one
I have no idea who first started grounding the mast to the ground block, but it has caught on. The concept is simple. A 10 awg copper can handle the grounding requirements of both the 17 awg CCS and the 14 awg coax ground. The ground block combines the two grounds into one. This is a logical adaption of the NEC. While not to the letter of the code, it does meet the spirit of the code. This is why I so strongly believe that installers MUST understand the code. When they are faced with a situation where you cannot meet the codes requirements, only with an understanding of the code can you hope to find an alternative means, that still provides a safe installation.
I would like to thank AntAltMike for a pleasant conversation. To me this is what forums do best. Provide a means for professionals to discuss issues.